TODO: |
|
- Remove this; (step 2) "This is the user name that you will log into Striker as and the name of the user that owns the database" |
|
- Being set to the gateway, not the default DNS - "This is the domain name server(s) to use when resolving domain names. You can specify 2 or more, separated by commas." |
|
- The web UI password isn't being set properly during Striker stage-2 setup |
|
- Changing the password doesn't log out active webui sessions. |
|
- host_health is a duplicate of 'health' |
|
|
|
============ |
|
|
|
# ScanCore post-scan logic; |
|
|
|
Sole node: |
|
1. Evaluate critical shutdown only, if hosting VMs. |
|
2. If not hosting VMs, load-shed if over-heat / power loss for more than 120 seconds |
|
|
|
Action options; |
|
1. Do nothing |
|
2. Pull servers |
|
3. Shut down (once servers are gone) |
|
4. Shut down (gracefully stop servers) |
|
|
|
|
|
* Peer not available |
|
- Thermal is critical, gracefully shut down. |
|
- Power is strongest UPS below ten minutes and time on batteries is over 2 minutes, graceful shut down |
|
* Peer available |
|
- If one node is healthier than the other; |
|
- If we're sicker, do nothing until we have no servers |
|
- If we're healthier, after two minutes, pull |
|
- If health is equal; |
|
- Both nodes have servers; |
|
- Decide who can be evacuated fastest, in case load shed needed. |
|
- Both nodes on batteries or in warning temp for more than 2 minutes; |
|
- If we're the designated survivor, pull servers. |
|
- If we're the sacrifice, wait for the servers to be taken off of us, then shut down. |
|
- Peer has servers, we don't |
|
- If thermal warning or both/all UPSes on batter for two minutes+, shut down |
|
- We have servers, peer doesn't. |
|
- Keep running |
|
|
|
|
|
|
|
1.1 - Our peer may pull from us. |
|
2. - Not Hosting Servers |
|
2.1 - |
|
|
|
|
|
Jenkins; |
|
|
|
Initial setup: |
|
export NODE_NAME=anvil-ci-bm |
|
export python=python3 |
|
./ci-update-yum |
|
|
|
============ |
|
|
|
DISABLE KSM! |
|
- https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/7/html/virtualization_tuning_and_optimization_guide/chap-ksm |
|
|
|
NEXT; - |
|
|
|
RHEL 8 package changes: |
|
chrony replaces ntp |
|
cockpit replaces virt-manager (deprecated) |
|
e1000e replaces e1000 driver |
|
tmux replaces screen |
|
iproute2 replaces bridge-utils (See "ip link" and man bridge.) |
|
|
|
|
|
==] UEFI Setup [====================================================================== |
|
ignoredisk --only-use=vdb,vda |
|
clearpart --none --initlabel |
|
part raid.312 --fstype="mdmember" --ondisk=vda --size=19966 |
|
part raid.293 --fstype="mdmember" --ondisk=vdb --size=512 |
|
part raid.319 --fstype="mdmember" --ondisk=vdb --size=19966 |
|
part raid.286 --fstype="mdmember" --ondisk=vda --size=512 |
|
raid pv.326 --device=pv1 --fstype="lvmpv" --level=RAID1 raid.312 raid.319 |
|
raid /boot/efi --device=efi --fstype="efi" --level=RAID1 --fsoptions="umask=0077,shortname=winnt" --label=efi raid.286 raid.293 |
|
volgroup striker_vg0 --pesize=4096 pv.326 |
|
logvol swap --fstype="swap" --size=4096 --name=lv_swap --vgname=striker_vg0 |
|
logvol / --fstype="xfs" --size=15852 --label="lv_root" --name=lv_root --vgname=striker_vg0 |
|
====================================================================================== |
|
|
|
DOCS; - |
|
- Explanation of 'comps.xml' (package grouping) - https://pagure.io/fedora-comps |
|
- Firewalld |
|
- https://www.digitalocean.com/community/tutorials/how-to-set-up-a-firewall-using-firewalld-on-centos-7 |
|
- PXE; |
|
- https://docs.fedoraproject.org/en-US/fedora/f28/install-guide/advanced/Network_based_Installations/ |
|
- https://docs.fedoraproject.org/en-US/Fedora/26/html/Installation_Guide/chap-pxe-server-setup.html |
|
- UEFI PXE notes - https://www.syslinux.org/wiki/index.php?title=PXELINUX#UEFI |
|
- How to write a NetworkManager dispatcher script to apply ethtool commands? - https://access.redhat.com/solutions/2841131 |
|
- Setup nodes to log to striker? - https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/7/html/networking_guide/sec-configuring_netconsole |
|
- Pacemaker can be monitored via SNMP - https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/7/html/high_availability_add-on_reference/s1-snmpandpacemaker-HAAR |
|
- corosync.conf - https://access.redhat.com/articles/3185291 |
|
|
|
==== |
|
|
|
Network planning; |
|
|
|
10.x.y.z / 255.255.0.0 |
|
10.x.y.z / 255.255.0.0 |
|
|
|
x = Network; |
|
- BCN = 200 + network |
|
ie: BCN1 = 10.201.y.z |
|
BCN2 = 10.202.y.z |
|
- SN = 100 + network |
|
ie: SN1 = 10.101.y.z |
|
SN2 = 10.102.y.z |
|
|
|
y = Device Type. |
|
Foudation Pack; |
|
1. Switches |
|
2. PDUs |
|
3. UPSes |
|
4. Strikers |
|
5. Striker IPMI (BCN only) |
|
|
|
Anvil! systems; |
|
1st - 10 = Node IP |
|
11 = Node IPMI |
|
2nd - 12 = Node IP |
|
13 = Node IPMI |
|
3rd - 14 = Node IP |
|
15 = Node IPMI |
|
N... |
|
|
|
z = Device Sequence |
|
- Foundation pack devices are simple sequence |
|
- Anvils; .1 = node 1, .2 = node 2, .3 = dr |
|
|
|
==== |
|
|
|
RHEL 8 Firewall |
|
- https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/8-beta/html/configuring_and_managing_networking/assembly_using-firewalls_configuring-networking-with-gnome-gui |
|
|
|
============================= |
|
|
|
Ports we care about |
|
|
|
Porto Number Used by Nets Description |
|
TCP 2224 pcsd bcn It is crucial to open port 2224 in such a way that pcs from any node can talk to all nodes in the cluster, including itself. |
|
UDP 5404 corosync bcn Required on corosync nodes if corosync is configured for multicast UDP |
|
UDP 5405 corosync bcn Required on all corosync nodes (needed by corosync) |
|
TCP 7788+ drbd sn 1 port per resource |
|
TCP 49152-49215 virsh bcn live migration - migration_port_min and migration_port_max attributes in the /etc/libvirt/qemu.conf |
|
|
|
NOTE: DHCP listens to raw sockets and ignores firewalld rules. We need to stop dhcpd directly - https://kb.isc.org/docs/aa-00378 |
|
|
|
* After all changes; |
|
firewall-cmd --zone=public --add-port=49152-49215/tcp --permanent |
|
firewall-cmd --reload |
|
|
|
- Paths |
|
If we want to create services or helpers later, look under - /usr/lib/firewalld/ |
|
Core firewalld configs, including defaults zones, etc - /etc/firewalld/ |
|
|
|
* Zones are meant to deal with dynamic environments and aren't that useful in mostly static server environments |
|
* Use 'firewall-cmd' WITHOUT '--permanent' for things like enabling the VNC port for a server. Use '--permanent' for everything else. |
|
==== |
|
|
|
Striker as PXE server |
|
==== |
|
|
|
|
|
# Bootloader for BIOS |
|
OS="fedora28" |
|
mkdir /var/lib/tftpboot/ |
|
cp $(anvil source)/pxe/tftpboot/bios/* /var/lib/tftpboot/ |
|
chmod 755 /var/lib/tftpboot/* |
|
|
|
# Bootloader for UEFI |
|
cp $(anvil source)/pxe/tftpboot/uefi/* /var/lib/tftpboot/uefi/ |
|
chmod 755 /var/lib/tftpboot/uefi/* |
|
|
|
# Copy kernel images for tftpboot downloads |
|
mkdir -p /var/lib/tftpboot/${OS} |
|
cp /lib/modules/$(uname -r)/vmlinuz /var/lib/tftpboot/${OS}/ |
|
mkinitrd /var/lib/tftpboot/${OS}/initrd.img $(uname -r) |
|
|
|
# Configs from anvil source |
|
rsync -av pxe/tftpboot/pxelinux.cfg/default root@f28-striker01:/var/lib/tftpboot/pxelinux.cfg/ |
|
rsync -av pxe/tftpboot/pxelinux/uefi root@f28-striker01:/var/lib/tftpboot/pxelinux/ |
|
==== |
|
|
|
DB stuff; |
|
|
|
Dump; |
|
su - postgres -c "pg_dump anvil" > /anvil.out |
|
|
|
Drop; |
|
su - postgres -c "dropdb anvil" && su - postgres -c "createdb --owner admin anvil" && su - postgres -c "psql anvil" |
|
|
|
Reload the DB; |
|
su - postgres -c "dropdb anvil" && su - postgres -c "createdb --owner admin anvil" && su - postgres -c "psql anvil < /anvil.out" && su - postgres -c "psql anvil" |
|
|
|
|
|
|
|
Changes made using tools such as nmcli do not require a reload but do require the associated interface to be put down and then up again. That can be done by using commands in the following format: |
|
* nmcli dev disconnect interface-name |
|
Followed by: |
|
* nmcli con up interface-name |
|
|
|
NOTE: RHEL doesn't support direct-cabled bonds - https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/7/html/networking_guide/ch-configure_network_bonding |
|
|
|
ifcfg-X config Notes - /usr/share/doc/initscripts-*/sysconfig.txt (Look for the sections describing files /etc/sysconfig/network and /etc/sysconfig/network-scripts/ifcfg-<interface-name>); |
|
- man 5 nm-settings-ifcfg-rh |
|
- https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/7/html/networking_guide/sec-Using_Channel_Bonding#s3-modules-bonding-directives |
|
- /usr/share/doc/kernel-doc-*/Documentation/networking/bonding.txt |
|
iface |
|
* PREFIXx overrules NETMASKx. Use PREFIXx, not NETMASKx. |
|
* The 'x' suffice for PREFIX, NETMASK, etc start at 0 and must count up by 1 at a time. |
|
* ZONE will be useful for the firewall stuff later. |
|
* ETHTOOL_OPTS is deprecated, replaced by using udev rules |
|
* initscripts interpret PEERDNS=no to mean "never touch resolv.conf". NetworkManager interprets it to say "never add automatic (DHCP, PPP, VPN, etc.) nameservers to resolv.conf". |
|
Bond |
|
* resend_igmp & num_unsol_na={1~255} may help if a switch is slow to notice traffic has moved to the new interface. default is 1. Each update is send 200ms apart. |
|
* Bridged interfaces should use BRIDGE_UUID="", _not_ BRIDGE="". The former causes the later to be ignored and the later is only used for possible compatibility reasons. |
|
Bridge |
|
* STP=no is default, we'll test 'yes'. |
|
* DOMAIN="<client_domain>" |
|
|
|
======= |
|
virt-manager stores information in dconf-editor -> /org/virt-manager/virt-manager/connections ($HOME/.config/dconf/user) |
|
|
|
==== dconf read /org/virt-manager/virt-manager/connections/uris |
|
['qemu+ssh://root@localhost/system', 'qemu+ssh://root@wp-a01n02.remote/system', 'qemu+ssh://root@an-nas02.kw01.alteeve.ca/system', 'qemu+ssh://root@hb-a01n01.remote/system', 'qemu+ssh://root@hb-a01n02.remote/system', 'qemu:///system'] |
|
==== dconf read /org/virt-manager/virt-manager/connections/autoconnect |
|
['qemu+ssh://root@localhost/system'] |
|
==== |
|
|
|
# Web - TODO: Setup to auto-use "Let's Encrypt", but make sure we have an offline fall-back |
|
|
|
# SELinux |
|
restorecon -rv /var/www |
|
|
|
============================================================= |
|
|
|
* Network; |
|
** {bc,if,s}nX_{link,bond,bridge}Y naming |
|
** firewall; - https://access.redhat.com/documentation/en-us/red_hat_enterprise_linux/7/html/high_availability_add-on_reference/s1-firewalls-haar |
|
firewall-cmd --permanent --add-service=high-availability |
|
firewall-cmd --add-service=high-availability |
|
firewall-cmd --reload |
|
|
|
|
|
* Cluster Config; |
|
==== Both nodes |
|
echo Initial1 | passwd hacluster --stdin |
|
systemctl start pcsd.service |
|
systemctl enable pcsd.service |
|
systemctl disable libvirtd.service |
|
systemctl stop libvirtd.service |
|
==== One node |
|
pcs host auth el8-a01n01 el8-a01n02 -u hacluster -p "secret" |
|
|
|
### VMs |
|
pcs cluster setup m3-anvil-01 el8-a01n01 el8-a01n02 |
|
pcs cluster start --all |
|
pcs stonith create virsh_node1 fence_virsh pcmk_host_list="el8-a01n01" ipaddr="192.168.122.1" passwd="secret" login="root" delay="15" port="el8-a01n01" op monitor interval="60" |
|
pcs stonith create virsh_node2 fence_virsh pcmk_host_list="el8-a01n02" ipaddr="192.168.122.1" passwd="secret" login="root" port="el8-a01n02" op monitor interval="60" |
|
|
|
### Real iron. |
|
pcs stonith create ipmilan_node1 fence_ipmilan pcmk_host_list="mk-a02n01" ipaddr="10.201.13.1" password="another secret p" username="admin" delay="15" op monitor interval="60" |
|
pcs stonith level add 1 mk-a02n01 ipmilan_node1 |
|
|
|
pcs stonith create ipmilan_node2 fence_ipmilan pcmk_host_list="mk-a02n02" ipaddr="10.201.13.2" password="another secret p" username="admin" op monitor interval="60" |
|
pcs stonith level add 1 mk-a02n02 ipmilan_node2 |
|
|
|
pcs stonith create apc_snmp_node1_psu1 fence_apc_snmp pcmk_host_list="mk-a02n01" pcmk_off_action="reboot" ip="10.201.2.3" port="3" power_wait="5" op monitor interval="60" |
|
pcs stonith create apc_snmp_node1_psu2 fence_apc_snmp pcmk_host_list="mk-a02n01" pcmk_off_action="reboot" ip="10.201.2.4" port="3" power_wait="5" op monitor interval="60" |
|
pcs stonith level add 2 mk-a02n01 apc_snmp_node1_psu1,apc_snmp_node1_psu2 |
|
|
|
pcs stonith create apc_snmp_node2_psu1 fence_apc_snmp pcmk_host_list="mk-a02n02" pcmk_off_action="reboot" ip="10.201.2.3" port="4" power_wait="5" op monitor interval="60" |
|
pcs stonith create apc_snmp_node2_psu2 fence_apc_snmp pcmk_host_list="mk-a02n02" pcmk_off_action="reboot" ip="10.201.2.4" port="4" power_wait="5" op monitor interval="60" |
|
pcs stonith level add 2 mk-a02n02 apc_snmp_node2_psu1,apc_snmp_node2_psu2 |
|
|
|
pcs stonith create delay_node1 fence_delay pcmk_host_list="mk-a02n01" wait="60" op monitor interval="60" |
|
pcs stonith level add 3 mk-a02n01 delay_node1 |
|
|
|
pcs stonith create delay_node2 fence_delay pcmk_host_list="mk-a02n02" wait="60" op monitor interval="60" |
|
pcs stonith level add 3 mk-a02n02 delay_node2 |
|
|
|
# Either case |
|
pcs property set stonith-max-attempts=INFINITY |
|
pcs property set stonith-enabled=true |
|
|
|
### TODO: Look into 'priority-fencing-delay' |
|
|
|
|
|
# Create a new server resource, stopped, create the location constraint (higher == preferred), then start. |
|
pcs resource create srv01-test ocf:alteeve:server name="srv01-test" meta allow-migrate="true" target-role="stopped" op monitor interval="60" start timeout="INFINITY" on-fail="block" stop timeout="INFINITY" on-fail="block" migrate_to timeout="INFINITY" |
|
|
|
pcs constraint location srv01-test prefers mk-a02n01=200 mk-a02n02=100 |
|
pcs resource enable srv01-test |
|
- or - |
|
pcs resource update srv01-test ocf:alteeve:server name="srv01-test" meta allow-migrate="true" target-role="stopped" op monitor interval="60" start timeout="INFINITY" on-fail="block" stop timeout="INFINITY" on-fail="block" migrate_to timeout="INFINITY" |
|
|
|
# Test |
|
stonith_admin --fence el8-a01n02 --verbose; crm_error $? |
|
|
|
|
|
|
|
pcs resource create srv01-test ocf:alteeve:server name="srv01-test" meta allow-migrate="true" target-role="started" op monitor interval="60" start timeout="INFINITY" on-fail="block" stop timeout="INFINITY" on-fail="block" migrate_to timeout="INFINITY" |
|
pcs constraint location srv01-test prefers el8-a01n01=200 el8-a01n02=100 |
|
|
|
|
|
|
|
stonith-max-attempts=INFINITY |
|
cluster-recheck-interval puts an upper bound on the "i give up" time |
|
|
|
==== DRBD notes |
|
|
|
* resources can contain an US-ASCII character, except for spaces |
|
* A resource is a single replication stream for 1 or more resources, max 65.535 vols per resource |
|
* DRBD does, however, ship with an LVM integration facility that automates the creation of LVM snapshots immediately before synchronization. This ensures that a consistent copy of the data is always available on the peer, even while synchronization is running. See Using automated LVM snapshots during DRBD synchronization for details on using this facility. |
|
** https://docs.linbit.com/docs/users-guide-9.0/#s-lvm-snapshots |
|
* Checksum-based synchronization computes a block's hash on source and target and skips if matching, possibly making resync much faster for blocks rewritten with the same data, but at the cost of CPU. Make this a user-configurable option under the advanced tab. |
|
* Suspended replication allows congested replication links to suspend replication, leaving the peer in a consistent state, but allowing the primary to "pull ahead". When the congestion passes, the delta resyncs. Make this a user-configurable option with scary warnings. |
|
* Online verification can (should?) be run periodically on the server host (verification source will overwrite deltas on the verification target). Perhaps schedule to run once/month? Do resource sequentially as this places a CPU load on the nodes. |
|
* Replication traffic integrity checking uses a given available kernel crypto to verify data integrity on transmission to the peer. If the replicated block can not be verified against the digest, the connection is dropped and immediately re-established; because of the bitmap the typical result is a retransmission. |
|
** Make an option in the advanced tab. Test to see overhead this adds. Choose the lowest overhead algo (within reason) |
|
* Support for disk flushes might be something we want to disable, as it seems to force write-through even with a function FBWC/BBU. Need to test. |
|
* Note; "Inconsistent" is almost always useless. "Consistent" and "Outdated" are able to be used safely, just without whatever happened on the peer after. |
|
* Truck based replication, also known as disk shipping, is a means of preseeding a remote site with data to be replicated, by physically shipping storage media to the remote site. |
|
* Make sure that selinux doesn't block DRBD comms over the SN |
|
* See "5.15.1. Growing on-line" for growing a DRBD resource |
|
** Shrinking online is ONLY possible if the metadata is external. Worth creating *_md LVs? Offline requires backing up and restoring the MD |
|
|
|
Provisioning a server will need to: |
|
* Create the LVs |
|
* Open up the DRBD ports |
|
* Create the DRBD resource(s); Find the lowest free rX.res, create it locally and on the peer (if up), |
|
|
|
firewall-cmd --zone=public --permanent --add-port=7788-7790/tcp |
|
firewall-cmd --reload |
|
|
|
* Provision the server via virt-install |
|
* push the new XML to striker such that the peer's anvil daemon picks it up and writes it out. |
|
|
|
[root@el8-a01n01 drbd.d]# drbdsetup status r0 --verbose --statistics |
|
r0 node-id:1 role:Primary suspended:no |
|
write-ordering:flush |
|
volume:0 minor:0 disk:UpToDate quorum:yes |
|
size:10485404 read:9682852 written:0 al-writes:0 bm-writes:0 upper-pending:0 lower-pending:0 al-suspended:no blocked:no |
|
el8-a01n02.alteeve.com node-id:0 connection:Connected role:Secondary congested:no |
|
volume:0 replication:SyncSource peer-disk:Inconsistent done:92.29 resync-suspended:no |
|
received:0 sent:9679140 out-of-sync:808144 pending:6 unacked:3 |
|
|
|
[root@el8-a01n02 ~]# cat /sys/kernel/debug/drbd/resources/r0/connections/el8-a01n01.alteeve.com/0/proc_drbd |
|
0: cs:SyncSource ro:Primary/Secondary ds:UpToDate/Inconsistent C r----- |
|
ns:24360 nr:10485404 dw:10485404 dr:25420 al:0 bm:0 lo:0 pe:[0;0] ua:0 ap:[0;0] ep:1 wo:2 oos:10461044 |
|
[>....................] sync'ed: 0.3% (10212/10236)M |
|
finish: 0:50:01 speed: 3,480 (5,020 -- 3,480) K/sec |
|
99% sector pos: 20970808/20970808 |
|
resync: used:0/61 hits:557 misses:2 starving:0 locked:0 changed:1 |
|
act_log: used:0/1237 hits:0 misses:0 starving:0 locked:0 changed:0 |
|
blocked on activity log: 0 |
|
|
|
[root@el8-a01n02 ~]# drbdadm primary r0 |
|
r0: State change failed: (-1) Multiple primaries not allowed by config |
|
Command 'drbdsetup primary r0' terminated with exit code 11 |
|
|
|
[root@el8-a01n02 ~]# drbdadm net-options --allow-two-primaries=yes r0 |
|
[root@el8-a01n02 ~]# drbdadm net-options --allow-two-primaries=no r0 |
|
|
|
drbdsetup show all |
|
drbdsetup show all --show-defaults |
|
|
|
== virt-install stuff |
|
* Get a list of --os-variants: 'osinfo-query os' |
|
* virt-install --print-xml (or --transient) |
|
* Migate; |
|
# For all resources under the server; |
|
#drbdadm net-options r0 --allow-two-primaries=yes |
|
|
|
drbdsetup net-options srv01-c7_0 2 --_name=m3-a02n01.alteeve.com --csums-alg=md5 --data-integrity-alg=md5 --after-sb-0pri=discard-zero-changes --after-sb-1pri=discard-secondary --after-sb-2pri=disconnect --protocol=C --fencing=resource-and-stonith --allow-two-primaries=yes |
|
drbdsetup net-options srv01-c7_0 2 --_name=m3-a02n01.alteeve.com --csums-alg=md5 --data-integrity-alg=md5 --after-sb-0pri=discard-zero-changes --after-sb-1pri=discard-secondary --after-sb-2pri=disconnect --protocol=C --fencing=resource-and-stonith --allow-two-primaries=yes |
|
|
|
|
|
# Adding a second volume to a running resource; |
|
- I wonder if you'd have the same results if you could get vol1 into an UpToDate/UpToDate state using the drbdsetup equivalent of drbdadm new-current-uuid --clear-bitmap <res> |
|
|
|
# Migrate: |
|
|
|
virsh -c qemu+ssh://root@m3-a02n02.alteeve.com/system list |
|
|
|
virsh migrate --unsafe --undefinesource --live srv01-c7 qemu+ssh://m3-a02n01.alteeve.com/system |
|
virsh -c qemu+ssh://root@m3-a02n02.alteeve.com/system migrate --undefinesource --live srv01-c7 qemu+ssh://m3-a02n01.alteeve.com/system |
|
|
|
# Again for all resource under the server; |
|
drbdadm net-options r0 --allow-two-primaries=no |
|
|
|
drbdsetup net-options <resource> <target_node_id> --_name=<target_node_name> --allow-two-primaries=yes |
|
virsh migrate --undefinesource --live <server> qemu+ssh://<target_node>/system |
|
drbdsetup net-options <resource> <target_node_id> --_name=<target_node_name> --allow-two-primaries=no |
|
|
|
pcs constraint list --full |
|
Location Constraints: |
|
Resource: srv01-c7 |
|
Enabled on: m3-a02n02.alteeve.com (score:50) (id:location-srv01-c7-m3-a02n02.alteeve.com-50) |
|
pcs constraint remove location-srv01-c7-m3-a02n02.alteeve.com-50 |
|
|
|
|
|
|
|
Set to 90% of BCN bandwidth |
|
migrate-setspeed domain bandwidth |
|
Set the maximum migration bandwidth (in MiB/s) for a domain which is being migrated to another host. bandwidth is interpreted as an |
|
unsigned long long value. Specifying a negative value results in an essentially unlimited value being provided to the hypervisor. The |
|
hypervisor can choose whether to reject the value or convert it to the maximum value allowed. |
|
|
|
migrate-getspeed domain |
|
Get the maximum migration bandwidth (in MiB/s) for a domain. |
|
|
|
|
|
# Provision servers |
|
mkdir /mnt/anvil/{provision,files,archive,definitions} |
|
|
|
|
|
== Resource Agent; https://github.com/ClusterLabs/resource-agents/blob/master/doc/dev-guides/ra-dev-guide.asc |
|
|
|
* A resource agent receives all configuration information about the resource it manages via environment variables. The names of these environment variables are always the name of the resource parameter, prefixed with OCF_RESKEY_. For example, if the resource has an ip parameter set to 192.168.1.1, then the resource agent will have access to an environment variable OCF_RESKEY_ip holding that value. |
|
|
|
|
|
=== |
|
|
|
When stopping a server; |
|
14:03 < lge> "on-fail: block" |
|
14:03 < lge> is per operation type. |
|
14:08 < lge> anyways, you can also "on-fail: retry" |
|
|
|
OK, set the stop timeout to 60, set 'on-fail: block" and set the failure-timeout to 60 and see how pacemaker reacts. |
|
failure-timeout |
|
|
|
=== |
|
|
|
Migrate servers; |
|
|
|
- Let ScanCore set 'node-health' attribute (http://clusterlabs.org/pacemaker/doc/en-US/Pacemaker/1.1/html-single/Pacemaker_Explained/index.html#s-node-health) |
|
- Set 'migration-limit' to '1' to enforce serial live migration (http://clusterlabs.org/pacemaker/doc/en-US/Pacemaker/1.1/html-single/Pacemaker_Explained/index.html#s-cluster-options). |
|
|
|
Migrate a single server by setting a location constraint against the node we want the VM off of. |
|
- If anything goes wrong, the server will enter a blocked state in pacemaker. |
|
- Recovery needs to be 'unmanage -> clean' to avoid a stop call. |
|
11:57 <@kgaillot> for your design, that sounds right. between cleanup and manage, i'd make sure there was a PE run without any pending actions blocked by the unmanaging -- you can either look at the logs on the DC, run "crm_simulate -SL", or just check the status for a bit |
|
11:58 <@kgaillot> you can play around with it by putting a higher preference on the to-be-cleaned node, to make sure it *does* move when you re-manage. that way you can see what logs/simulate/status look like |
|
|
|
12:07 <@kgaillot> i'm thinking if you do crm_resource --reprobe instead of cleanup in the above sequence, that should prevent anything unexpected |
|
12:07 <@kgaillot> unmanage -> adjust preferences if needed -> reprobe resource -> wait for probe results to come back in, and if status looks good -> re-manage |
|
12:08 <@kgaillot> the reprobe will wipe the entire resource history and fail counts for the resource, causing pacemaker to recheck the current status on all nodes. if the status then shows the resource running where you expect/want it, with no errors, then it's not going to do anything further |
|
12:09 <@kgaillot> (in 2.0, cleanup only erases the history where the resource has failed, while reprobe erases the history regardless) |
|
12:13 <@kgaillot> if there are no failures in the resource history, there should be no risk of a full stop. if there is no resource history at all, then after reprobe, there should be no risk of any actions (assuming you've set up location preferences and stickiness how you want them) |
|
|
|
Recover from a failed migration; |
|
|
|
reset location to prefer current host -> unmanage resource -> cleanup resource -> manage resource |
|
|
|
(running on node 2, so re-add location constraint - basically, make sure location constraint favours current host) |
|
|
|
|
|
https://pykickstart.readthedocs.io/en/latest/kickstart-docs.html#chapter-1-introduction |
|
|
|
==== Sample kickstart for Fedora28 netinstall |
|
#version=DEVEL |
|
ignoredisk --only-use=vda |
|
# Partition clearing information |
|
clearpart --none --initlabel |
|
# Use graphical install |
|
graphical |
|
# Use network installation |
|
url --url="http://10.1.4.1/rhel8/x86_64/iso/" |
|
# Keyboard layouts |
|
keyboard --vckeymap=us --xlayouts='us' |
|
# System language |
|
lang en_CA.UTF-8 |
|
|
|
# Network information |
|
network --bootproto=dhcp --device=ens3 --ipv6=auto --activate |
|
network --hostname=localhost.localdomain |
|
# Root password |
|
rootpw --iscrypted $6$fyAht.3wBVlRGgqG$5dqIv2NrBD87uA51fxuoic/t2G93pXPUjVlh27Avg20ZGY409SK8cMVgABswF.krJSVIyoHfIChXNfpP/qTjI1 |
|
# Run the Setup Agent on first boot |
|
firstboot --enable |
|
# Do not configure the X Window System |
|
skipx |
|
# System services |
|
services --enabled="chronyd" |
|
# System timezone |
|
timezone Etc/GMT --isUtc |
|
# System bootloader configuration |
|
bootloader --location=mbr --boot-drive=vda |
|
|
|
%packages |
|
@^server-product-environment |
|
|
|
%end |
|
|
|
%addon com_redhat_kdump --disable --reserve-mb='128' |
|
|
|
%end |
|
|
|
%anaconda |
|
pwpolicy root --minlen=6 --minquality=1 --notstrict --nochanges --notempty |
|
pwpolicy user --minlen=6 --minquality=1 --notstrict --nochanges --emptyok |
|
pwpolicy luks --minlen=6 --minquality=1 --notstrict --nochanges --notempty |
|
%end |
|
==== |
|
|
|
==== M3 Striker Kickstart |
|
# Setion 1 |
|
# Command section – Refer to Chapter 2 for a list of kickstart options. You must include the required options. |
|
|
|
|
|
### NOTE: The %packages, %pre, %pre-install, %post, %onerror, and %traceback sections are all required to be closed with %end |
|
# Section 2 |
|
# The %packages section – Refer to Chapter 3 for details. |
|
|
|
|
|
# Section 3: |
|
# The %pre, %pre-install, %post, %onerror, and %traceback sections – These sections can be in any order and are not required. Refer to Chapter 4, Chapter 5, and Chapter 6 for details. |
|
==== |
|
|
|
0 root@pulsar:/var/lib/libvirt/images# dev_PATH=$(udevadm info /dev/sdb | grep -e ID_PATH=) |
|
0 root@pulsar:/var/lib/libvirt/images# if [[ $dev_PATH == *"usb"* ]]; then echo "USB drive"; elif [[ $dev_PATH == *"nvme"* ]]; then echo "NVMe drive"; elif [[ $dev_PATH == *"ata"* ]]; then echo "SATA drive"; elif [[ $dev_PATH == *"scsi"* ]]; then echo "SCSI drive"; fi |
|
USB drive |
|
0 root@pulsar:/var/lib/libvirt/images# dev_PATH=$(udevadm info /dev/sda | grep -e ID_PATH=) |
|
0 root@pulsar:/var/lib/libvirt/images# if [[ $dev_PATH == *"usb"* ]]; then echo "USB drive"; elif [[ $dev_PATH == *"nvme"* ]]; then echo "NVMe drive"; elif [[ $dev_PATH == *"ata"* ]]; then echo "SATA drive"; elif [[ $dev_PATH == *"scsi"* ]]; then echo "SCSI drive"; fi |
|
SATA drive |
|
0 root@pulsar:/var/lib/libvirt/images# dev_PATH=$(udevadm info /dev/nvme0n1 | grep -e ID_PATH=) |
|
0 root@pulsar:/var/lib/libvirt/images# if [[ $dev_PATH == *"usb"* ]]; then echo "USB drive"; elif [[ $dev_PATH == *"nvme"* ]]; then echo "NVMe drive"; elif [[ $dev_PATH == *"ata"* ]]; then echo "SATA drive"; elif [[ $dev_PATH == *"scsi"* ]]; then echo "SCSI drive"; fi |
|
NVMe drive |
|
[root@localhost ~]# dev_PATH=$(udevadm info /dev/sda | grep -e ID_PATH=) |
|
[root@localhost ~]# if [[ $dev_PATH == *"usb"* ]]; then echo "USB drive"; elif [[ $dev_PATH == *"nvme"* ]]; then echo "NVMe drive"; elif [[ $dev_PATH == *"ata"* ]]; then echo "SATA drive"; elif [[ $dev_PATH == *"scsi"* ]]; then echo "SCSI drive"; fi |
|
SCSI drive |
|
|
|
|
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sdb/device/model |
|
Flash Disk |
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sda/device/model |
|
SanDisk SDSSDXPS |
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/nvme0n1/device/model |
|
INTEL SSDPEKKW512G7 |
|
|
|
### Stuff only NVMe has |
|
1 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/nvme0n1/device/subsysnqn |
|
nqn.2014.08.org.nvmexpress:80868086BTPY63650FPG512F INTEL SSDPEKKW512G7 |
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sda/device/subsysnqn |
|
cat: /sys/class/block/sda/device/subsysnqn: No such file or directory |
|
1 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sdb/device/subsysnqn |
|
cat: /sys/class/block/sdb/device/subsysnqn: No such file or directory |
|
|
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/nvme0n1/device/serial |
|
BTPY63650FPG512F |
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sda/device/serial |
|
cat: /sys/class/block/sda/device/serial: No such file or directory |
|
1 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sdb/device/serial |
|
cat: /sys/class/block/sdb/device/serial: No such file or directory |
|
|
|
1 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/nvme0n1/device/transport |
|
pcie |
|
0 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sda/device/transport |
|
cat: /sys/class/block/sda/device/transport: No such file or directory |
|
1 root@pulsar:/var/lib/libvirt/images# cat /sys/class/block/sdb/device/transport |
|
cat: /sys/class/block/sdb/device/transport: No such file or directory |
|
|
|
|
|
|
|
Disk size: |
|
/sys/class/block/sda/size * <block size> |
|
|
|
===== |
|
man pages |
|
|
|
1 Executable programs or shell commands |
|
5 File formats and conventions eg /etc/passwd |
|
7 Miscellaneous (including macro packages and conventions), e.g. man(7), groff(7) |
|
8 System administration commands (usually only for root) |
|
|
|
A manual page consists of several sections. |
|
|
|
Conventional section names include NAME, SYNOPSIS, CONFIGURATION, DESCRIPTION, OPTIONS, EXIT STATUS, RETURN VALUE, ERRORS, ENVIRONMENT, FILES, VERSIONS, CONFORMING TO, NOTES, BUGS, EXAMPLE, AUTHORS, and SEE ALSO. |
|
|
|
The following conventions apply to the SYNOPSIS section and can be used as a guide in other sections. |
|
|
|
bold text type exactly as shown. |
|
italic text replace with appropriate argument. |
|
[-abc] any or all arguments within [ ] are optional. |
|
-a|-b options delimited by | cannot be used together. |
|
argument ... argument is repeatable. |
|
[expression] ... entire expression within [ ] is repeatable. |
|
|
|
|
|
==== |
|
|
|
======================================= |
|
|
|
chrissie's cluster script |
|
|
|
# Run these commands on all nodes: |
|
cp ../ifup-local /sbin |
|
/sbin/ifup-local |
|
pcs host auth -uhacluster -phacluster amy.chrissie.net anna.chrissie.net clara.chrissie.net fanny.chrissie.net |
|
|
|
if [ "$(hostname)" != "amy.chrissie.net" -a "$(hostname)" != "amy" ] |
|
then |
|
exit |
|
fi |
|
|
|
# and these on just one: |
|
pcs cluster setup taroxVMs amy.chrissie.net anna.chrissie.net clara.chrissie.net fanny.chrissie.net |
|
pcs cluster start --all |
|
sleep 30 |
|
|
|
pcs stonith create fence-virsh fence_virsh ipaddr=192.168.100.1 login=root passwd=christine pcmk_host_map="amy:rhel8-1;anna:rhel8-2;clara:rhel8-3;fanny:rhel8-4" |
|
|
|
|
|
|
|
if [ ! -e '/dev/an-a01n01_vg0/srv09-psql_0' ]; |
|
then |
|
/sbin/lvcreate -L 69GiB -n srv09-psql_0 an-a01n01_vg0 |
|
fi |
|
virt-install --connect qemu:///system \ |
|
--name srv09-psql \ |
|
--ram 4096 \ |
|
--arch x86_64 \ |
|
--vcpus 2 \ |
|
--cpu Nehalem,+fsgsbase \ |
|
--cdrom '/shared/files/Win2016_Server_64-bit_English.iso' \ |
|
--boot menu=on \ |
|
--disk path='/shared/files/virtio-win.iso',device=cdrom --force\ |
|
--os-variant win2k8 \ |
|
--network bridge=ifn_bridge1,model=virtio \ |
|
--disk path=/dev/an-a01n01_vg0/srv09-psql_0,bus=virtio,cache=writethrough \ |
|
--graphics spice \ |
|
--noautoconsole --wait -1 > /var/log/anvil-server_srv09-psql.log & |
|
|
|
|
|
# Migration; |
|
|
|
pcs constraint remove $(pcs constraint show --full | grep ban-srv07-el6 | perl -pe 's/^.*?id:(.*?)\)/$1/') |
|
|
|
|
|
# Attach a network interface: |
|
virsh attach-interface win2019_test bridge ifn_bridge1 --live --model virtio |
|
|
|
# Detach a network interface: |
|
virsh detach-interface win2019_test bridge --mac 52:54:00:ee:b5:1d |
|
|
|
# Change the MTU of a device; |
|
ip link set <dev> mtu 9000 |
|
|
|
# Change the MTU of an interface in windows (not tested yet - http://networking.nitecruzr.net/2007/11/setting-mtu-in-windows-vista.html) |
|
netsh interface ipv4 set subinterface "Local Area Connection" mtu=nnnn store=persistent |
|
|
|
yum install kernel-2.6.32-754.27.1.el6.x86_64 kernel-devel-2.6.32-754.27.1.el6.x86_64 kernel-headers-2.6.32-754.27.1.el6.x86_64 |
|
|
|
|
|
DRBD Notes; |
|
* c-max-rate is default 100M. Detect when the SN is 10Gbps and up to 750M |
|
* drbdsetup show <resource> --show-defaults <- shows defaults |
|
|
|
When a node comes online, and the peer and DR Host are both UpToDate, manually run the commands so that the |
|
restarting node connects to the DR first, so that it will sync from DR and minimize IO load on the peer node. |
|
The sequence of commands needed to up a resource are exposed by 'drbdadm up -d <res>'. Ie: |
|
|
|
[root@el8-a01n02 ~]# drbdadm -d up srv02-hi |
|
drbdsetup new-resource srv02-hi 1 --auto-promote=yes |
|
drbdsetup new-minor srv02-hi 2 0 |
|
drbdsetup new-peer srv02-hi 0 --_name=el8-a01n01 --allow-two-primaries=no --after-sb-0pri=discard-zero-changes --after-sb-1pri=discard-secondary --after-sb-2pri=disconnect --timeout=100 --protocol=C --fencing=resource-and-stonith |
|
drbdsetup new-peer srv02-hi 2 --_name=el8-a01dr01 --allow-two-primaries=no --after-sb-0pri=discard-zero-changes --after-sb-1pri=discard-secondary --after-sb-2pri=disconnect --timeout=100 --protocol=A --fencing=dont-care |
|
drbdsetup new-path srv02-hi 0 ipv4:10.101.10.2:7791 ipv4:10.101.10.1:7791 |
|
drbdsetup new-path srv02-hi 2 ipv4:10.101.10.2:7793 ipv4:10.101.10.3:7793 |
|
drbdmeta 2 v09 /dev/node_8da3d2fe/srv02-hi_0 internal apply-al |
|
drbdsetup attach 2 /dev/node_8da3d2fe/srv02-hi_0 /dev/node_8da3d2fe/srv02-hi_0 internal --disk-flushes=no --md-flushes=no |
|
drbdsetup connect srv02-hi 0 |
|
drbdsetup connect srv02-hi 2 |
|
|
|
Manual split brain recovery; |
|
# Both nodes; |
|
drbdadm disconnect <res> |
|
# Node to discard; |
|
drbdadm connect --discard-my-data <res> |
|
# Node to save data on; |
|
drbdadm connect <res> |
|
|
|
================== |
|
# Server srv01-sql, example showing two disks in one VM. |
|
resource srv01-sql { |
|
|
|
on mk-a02n01 { |
|
node-id 0; |
|
volume 0 { |
|
device /dev/drbd_srv01-sql_0 minor 0; |
|
disk /dev/rhel/srv01-sql_0; |
|
meta-disk internal; |
|
} |
|
volume 1 { |
|
device /dev/drbd_srv01-sql_1 minor 1; |
|
disk /dev/rhel/srv01-sql_1; |
|
meta-disk internal; |
|
} |
|
} |
|
|
|
on mk-a02n02 { |
|
node-id 1; |
|
volume 0 { |
|
device /dev/drbd_srv01-sql_0 minor 0; |
|
disk /dev/rhel/srv01-sql_0; |
|
meta-disk internal; |
|
} |
|
volume 1 { |
|
device /dev/drbd_srv01-sql_1 minor 1; |
|
disk /dev/rhel/srv01-sql_1; |
|
meta-disk internal; |
|
} |
|
} |
|
|
|
on mk-a02dr01 { |
|
node-id 2; |
|
volume 0 { |
|
device /dev/drbd_srv01-sql_0 minor 0; |
|
disk /dev/rhel_new-dr/srv01-sql_0; |
|
meta-disk internal; |
|
} |
|
volume 1 { |
|
device /dev/drbd_srv01-sql_1 minor 1; |
|
disk /dev/rhel_new-dr/srv01-sql_1; |
|
meta-disk internal; |
|
} |
|
} |
|
|
|
### NOTE: Remember to open the appropriate firewall port! |
|
# firewall-cmd --zone=SN1 --permanent --add-port=7788/tcp --permanent |
|
# firewall-cmd --zone=SN1 --permanent --add-port=7788/tcp |
|
|
|
connection { |
|
host mk-a02n01 address 10.101.12.1:7788; |
|
host mk-a02n02 address 10.101.12.2:7788; |
|
net { |
|
protocol C; |
|
fencing resource-and-stonith; |
|
} |
|
} |
|
connection { |
|
host mk-a02n01 address 10.101.12.1:7789; |
|
host mk-a02dr01 address 10.101.12.3:7789; |
|
net { |
|
protocol A; |
|
fencing dont-care; |
|
} |
|
} |
|
connection { |
|
host mk-a02n02 address 10.101.12.2:7790; |
|
host mk-a02dr01 address 10.101.12.3:7790; |
|
net { |
|
protocol A; |
|
fencing dont-care; |
|
} |
|
} |
|
} |
|
================== |
|
|
|
mediawiki on EL8 install notes (starting from a minimal install); |
|
|
|
dnf module reset php |
|
dnf module enable php:7.4 |
|
dnf install httpd php php-mysqlnd php-gd php-xml mariadb-server mariadb php-mbstring php-json \ |
|
vim postgresql-server postgresql-plperl bash-completion wget tar rsync mlocate php-pecl-apcu \ |
|
memcached php-pear icu php-intl php-pgsql bzip2 |
|
|
|
postgresql-setup --initdb |
|
systemctl start postgresql.service |
|
systemctl enable postgresql.service |
|
systemctl start httpd.service |
|
systemctl enable httpd.service |
|
systemctl start memcached.service |
|
systemctl enable memcached.service |
|
firewall-cmd --permanent --zone=public --add-service=http |
|
firewall-cmd --permanent --zone=public --add-service=https |
|
systemctl restart firewalld |
|
|
|
|
|
# diff -u /var/lib/pgsql/data/pg_hba.conf.orig /var/lib/pgsql/data/pg_hba.conf |
|
==== |
|
--- /var/lib/pgsql/data/pg_hba.conf.orig 2021-02-17 02:50:10.959000000 -0500 |
|
+++ /var/lib/pgsql/data/pg_hba.conf 2021-02-17 02:52:54.859000000 -0500 |
|
@@ -77,11 +77,12 @@ |
|
# TYPE DATABASE USER ADDRESS METHOD |
|
|
|
# "local" is for Unix domain socket connections only |
|
-local all all peer |
|
+local all postgres ident |
|
+local all all md5 |
|
# IPv4 local connections: |
|
-host all all 127.0.0.1/32 ident |
|
+host all all 127.0.0.1/32 md5 |
|
# IPv6 local connections: |
|
-host all all ::1/128 ident |
|
+host all all ::1/128 md5 |
|
# Allow replication connections from localhost, by a user with the |
|
# replication privilege. |
|
local replication all peer |
|
==== |
|
|
|
# diff -u /etc/php.ini.orig /etc/php.ini |
|
==== |
|
--- /etc/php.ini.orig 2021-02-17 02:56:32.293000000 -0500 |
|
+++ /etc/php.ini 2021-02-17 02:57:33.731000000 -0500 |
|
@@ -903,6 +903,7 @@ |
|
; 'extension='php_<ext>.dll') is supported for legacy reasons and may be |
|
; deprecated in a future PHP major version. So, when it is possible, please |
|
; move to the new ('extension=<ext>) syntax. |
|
+extension=php_pgsql.so |
|
|
|
;;;; |
|
; Note: packaged extension modules are now loaded via the .ini files |
|
==== |
|
|
|
Dell S4128T-ON Configuration |
|
|
|
# Terminal access using serial port on back on the switch (USB-B front connect seems flaky) |
|
screen /dev/ttyUSB0 115200 |
|
|
|
u: admin |
|
p: admin |
|
|
|
# Interface numbering (management port on the rear is 'mgmt 1/1/1'); |
|
OS10# show interface status |
|
|
|
-------------------------------------------------------------------------------------------------- |
|
Port Description Status Speed Duplex Mode Vlan Tagged-Vlans |
|
-------------------------------------------------------------------------------------------------- |
|
Eth 1/1/1 down 0 full A 1 - |
|
Eth 1/1/2 down 0 full A 1 - |
|
Eth 1/1/3 down 0 full A 1 - |
|
Eth 1/1/4 down 0 full A 1 - |
|
Eth 1/1/5 down 0 full A 1 - |
|
Eth 1/1/6 down 0 full A 1 - |
|
Eth 1/1/7 down 0 full A 1 - |
|
Eth 1/1/8 down 0 full A 1 - |
|
Eth 1/1/9 down 0 full A 1 - |
|
Eth 1/1/10 down 0 full A 1 - |
|
Eth 1/1/11 down 0 full A 1 - |
|
Eth 1/1/12 down 0 full A 1 - |
|
Eth 1/1/13 down 0 full A 1 - |
|
Eth 1/1/14 down 0 full A 1 - |
|
Eth 1/1/15 down 0 full A 1 - |
|
Eth 1/1/16 down 0 full A 1 - |
|
Eth 1/1/17 down 0 full A 1 - |
|
Eth 1/1/18 down 0 full A 1 - |
|
Eth 1/1/19 down 0 full A 1 - |
|
Eth 1/1/20 down 0 full A 1 - |
|
Eth 1/1/21 down 0 full A 1 - |
|
Eth 1/1/22 down 0 full A 1 - |
|
Eth 1/1/23 down 0 full A 1 - |
|
Eth 1/1/24 down 0 full A 1 - |
|
Eth 1/1/25 up 100G full A 1 - |
|
Eth 1/1/26 up 100G full A 1 - |
|
Eth 1/1/27 down 0 full A 1 - |
|
Eth 1/1/28 down 0 full A 1 - |
|
Eth 1/1/29 down 0 full A 1 - |
|
Eth 1/1/30 down 0 full A 1 - |
|
-------------------------------------------------------------------------------------------------- |
|
|
|
OS10# configure terminal |
|
OS10(config)# interface range ethernet 1/1/1-1/1/24 |
|
OS10(conf-range-eth1/1/1-1/1/24)# exit |
|
OS10(config)# interface range ethernet 1/1/1-1/1/24,1/1/27-1/1/30 |
|
OS10(conf-range-eth1/1/1-1/1/24,1/1/27-1/1/30)# exit |
|
|
|
|
|
# Configure management IP address |
|
OS10# configure terminal |
|
OS10(config)# interface mgmt 1/1/1 |
|
OS10(conf-if-ma-1/1/1)# no ip address dhcp |
|
OS10(conf-if-ma-1/1/1)# ip address 10.201.1.2/16 |
|
OS10(conf-if-ma-1/1/1)# <165>1 2021-04-02T12:23:40.141901+00:00 OS10 dn_alm 652 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %IP_ADDRESS_ADD: IP Address add is successful. IP 10.201.1.2/16 in VRF:default added successfully |
|
OS10(conf-if-ma-1/1/1)# no shutdown |
|
# Connected via SSH to confirm access: |
|
OS10(config)# |
|
<165>1 2021-04-02T12:25:49.956308+00:00 OS10 dn_alm 652 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %ALM_AUTH_EVENT: Authentication event was raised MESSAGE=pam_unix(sshd:session): session opened for user admin by (uid=0) |
|
<86>1 2021-04-02T12:25:49.501860+00:00 OS10 sshd 6512 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) pam_unix(sshd:session): session opened for user admin by (uid=0) |
|
<86>1 2021-04-02T12:25:51.795620+00:00 OS10 sshd 6527 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) pam_unix(sshd:session): session opened for user admin by (uid=0) |
|
<165>1 2021-04-02T12:25:51.957630+00:00 OS10 dn_alm 652 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %ALM_AUTH_EVENT: Authentication event was raised MESSAGE=pam_unix(sshd:session): session opened for user admin by (uid=0) |
|
OS10(config)# exit |
|
OS10# write memory |
|
|
|
### Set hostname: |
|
OS10# configure terminal |
|
OS10(config)# hostname zo-switch02 |
|
zo-switch02(config)# |
|
|
|
======] VLT Config [======= |
|
|
|
### Stacking is not a thing anymore, but VLT is its replacement. |
|
# On both switches; |
|
OS10# configure terminal |
|
OS10(config)# interface range ethernet 1/1/25-1/1/26 |
|
OS10(conf-range-eth1/1/25-1/1/26)# no shutdown |
|
OS10(conf-range-eth1/1/25-1/1/26)# no switchport |
|
<165>1 2021-04-02T11:47:05.731264+00:00 OS10 dn_alm 652 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %STP_ROOT_CHANGE: STP:Root Brg Chg RPVST root changed for vlan 1. |
|
<165>1 2021-04-02T11:47:05.739950+00:00 OS10 dn_alm 652 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %STP_ROOT_CHANGE: STP:Root Brg Chg My ID:f0d4.e250.cb8b OldRt:32769:f0d4.e250.c00b NewRt:32769:f0d4.e250.cb8b |
|
OS10(conf-range-eth1/1/25-1/1/26)# exit |
|
OS10(config)# vlt-domain 1 |
|
OS10(conf-vlt-1)# discovery-interface ethernet 1/1/25-1/1/26 |
|
# When this is done to the second switch; |
|
<165>1 2021-04-02T12:31:11.702525+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %IFM_ASTATE_UP: Interface admin state up :port-channel1000 |
|
<165>1 2021-04-02T12:31:11.707501+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %IFM_OSTATE_DN: Interface operational state is down :port-channel1000 |
|
<165>1 2021-04-02T12:31:11.720332+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %IFM_OSTATE_UP: Interface operational state is up :port-channel1000 |
|
<165>1 2021-04-02T12:31:11.845070+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %IFM_OSTATE_UP: Interface operational state is up :vlan4094 |
|
<165>1 2021-04-02T12:31:11.863978+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %VLT_PEER_UP: VLT unit 1 is up |
|
<165>1 2021-04-02T12:31:18.996716+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %VLT_ELECTION_ROLE: VLT unit 1 is elected as secondary |
|
<165>1 2021-04-02T12:31:19.087695+00:00 OS10 dn_alm 803 - - Node.1-Unit.1:PRI [event], Dell EMC (OS10) %IFM_OSTATE_UP: Interface operational state is up :vlan1 |
|
|
|
|
|
# Configure the same MAC address to the VLT on both switches: |
|
OS10# configure terminal |
|
OS10(config)# vlt-domain 1 |
|
OS10(conf-vlt-1)# vlt-mac 00:00:00:00:00:02 |
|
|
|
# show vlt 1 mismatch |
|
(If no issues, VLT is OK) |
|
|
|
# See how I am and my role (* == switch you're on) |
|
zo-switch02(config)# show vlt 1 role |
|
VLT Unit ID Role |
|
------------------------ |
|
* 1 secondary |
|
2 primary |
|
|
|
=====] VLAN Config [======== |
|
|
|
|
|
zo-switch02# configure terminal |
|
zo-switch02(config)# interface vlan 100 |
|
zo-switch02(conf-if-vl-100)# description BCN1 |
|
zo-switch02(conf-if-vl-100)# interface range ethernet 1/1/1-1/1/10 |
|
zo-switch02(conf-range-eth1/1/1-1/1/10)# switchport access vlan 100 |
|
zo-switch02(conf-range-eth1/1/1-1/1/10)# exot |
|
% Error: Unrecognized command. |
|
zo-switch02(conf-range-eth1/1/1-1/1/10)# exit |
|
zo-switch02(config)# interface range ethernet 1/1/11-1/1/14 |
|
zo-switch02(conf-range-eth1/1/11-1/1/14)# switchport access vlan 200 |
|
zo-switch02(conf-range-eth1/1/11-1/1/14)# exit |
|
zo-switch02(config)# interface range ethernet 1/1/15-1/1/24 |
|
zo-switch02(conf-range-eth1/1/15-1/1/24)# switchport access vlan 300 |
|
ezo-switch02(conf-range-eth1/1/15-1/1/24)# exit |
|
zo-switch02(config)# show vlan |
|
Codes: * - Default VLAN, M - Management VLAN, R - Remote Port Mirroring VLANs, |
|
@ – Attached to Virtual Network, P - Primary, C - Community, I - Isolated |
|
Q: A - Access (Untagged), T - Tagged |
|
NUM Status Description Q Ports |
|
* 1 Active A Eth1/1/27-1/1/30 |
|
A Po1000 |
|
100 Active BCN1 T Po1000 |
|
A Eth1/1/1-1/1/10 |
|
200 Active T Po1000 |
|
A Eth1/1/11-1/1/14 |
|
300 Active T Po1000 |
|
A Eth1/1/15-1/1/24 |
|
4094 Active T Po1000 |
|
|
|
|
|
### Delete a VLAN: |
|
|
|
zo-switch02(config)# no interface vlan 3400 |
|
zo-switch02(config)# show vlan |
|
|
|
|
|
# Configure VLANs. |
|
OS10(config)# interface range vlan 100,200,300 |
|
OS10(conf-range-vl-100,200,300)# exit |
|
OS10(config)# interface range ethernet 1/1/1-1/1/10 |
|
OS10(conf-range-eth1/1/1-1/1/10)# switchport access vlan 100 |
|
OS10(conf-range-eth1/1/1-1/1/10)# exit |
|
OS10(config)# interface range ethernet 1/1/11-1/1/14 |
|
OS10(conf-range-eth1/1/11-1/1/14)# switchport access vlan 200 |
|
OS10(conf-range-eth1/1/11-1/1/14)# exit |
|
OS10(config)# interface range ethernet 1/1/15-1/1/24 |
|
OS10(conf-range-eth1/1/15-1/1/24)# switchport access vlan 300 |
|
OS10(conf-range-eth1/1/15-1/1/24)# exit |
|
|
|
==================================== |
|
-=] Rename a resource (ex: srv09-few-tcpremote1 -> srv09-fea-tcpremote1) |
|
1. pacemaker - |
|
1.1 - Record current settings: |
|
# pcs resource config srv09-few-tcpremote1 |
|
Resource: srv09-few-tcpremote1 (class=ocf provider=alteeve type=server) |
|
Attributes: name=srv09-few-tcpremote1 |
|
Meta Attrs: allow-migrate=true target-role=Stopped |
|
Operations: migrate_from interval=0s timeout=600 (srv09-few-tcpremote1-migrate_from-interval-0s) |
|
migrate_to interval=0s timeout=86400 (srv09-few-tcpremote1-migrate_to-interval-0s) |
|
monitor interval=60 (srv09-few-tcpremote1-monitor-interval-60) |
|
notify interval=0s timeout=20 (srv09-few-tcpremote1-notify-interval-0s) |
|
start interval=0s on-fail=block timeout=300 (srv09-few-tcpremote1-start-interval-0s) |
|
stop interval=0s on-fail=block timeout=86400 (srv09-few-tcpremote1-stop-interval-0s) |
|
1.2 - Delete the resource |
|
|
|
|
|
==================================== |
|
|
|
|
|
# Hosts added or updated by the Anvil! on: [2021/04/17 16:24:52]: |
|
10.201.10.2 Could not get property: Refusing activation, D-Bus is shutting down Could not get property: Refusing activation, D-Bus is shutting down. Could not get property: Refusing activation, D-Bus is shutting down.bcn1 |
|
192.168.122.12 Could not get property: Refusing activation, D-Bus is shutting down.ifn1 |
|
10.101.10.2 Could not get property: Refusing activation, D-Bus is shutting down.sn1 |
|
|
|
|
|
ausearch -c 'drbdsetup' --raw | audit2allow -M my-drbdsetup && semodule -X 300 -i my-drbdsetup.pp |
|
|
|
|
|
May 02 13:35:21 zo-a01n02.zennioptical.com setroubleshoot[5333]: SELinux is preventing /usr/sbin/drbdsetup from create access on the netlink_generic_socket labeled drbd_t. For complete SELinux messages run: sealert -l 4079c288-db4a-4f44-a588-94f1dbfff269 |
|
May 02 13:35:21 zo-a01n02.zennioptical.com setroubleshoot[5333]: SELinux is preventing /usr/sbin/drbdsetup from create access on the netlink_generic_socket labeled drbd_t. |
|
If you believe that drbdsetup should be allowed create access on netlink_generic_socket labeled drbd_t by default. |
|
# ausearch -c 'drbdsetup' --raw | audit2allow -M my-drbdsetup |
|
# semodule -X 300 -i my-drbdsetup.pp |
|
|
|
|