* Cleaned up a log of logging to reduce the amount of log entries when running at log level 1.
* Bumped the scan-ipmitool default 'jump' range to 10c.
Signed-off-by: Digimer <digimer@alteeve.ca>
* Reworked scan-ipimitool so that on nodes and dr hosts, it only scans itself. On strikers, it scans all hosts found in active Anvil! systems with a host_ipmi entry. `
* For all agents, reduced log verbosity to not push too much noise into anvil.log while scancore is running in the background.
Signed-off-by: Digimer <digimer@alteeve.ca>
* Started work on Get->available_resources() that will take an 'anvil_uuid' and figure out what resources are still available for use by new servers or that can be added to existing servers.
* Fixed a bug in ScanCore->agent_startup() where tables weren't being generated properly from the agent's SQL file.
* Made Storage->change_mode() return silently if it's called without a mode being passed. This happens frequently and is harmless so it's not worth filling the logs with errors.
* Renamed the 'start_time' key to 'at_start' when recording files' MD5 sums in Storage->record_md5sums and ->check_md5sums.
* When we moved the directory scan logic out of the 'scancore' daemon and into 'Storage->scan_directory', the logic to record scan agent names in 'scancore::agent::<file>' was removed. This broke a few things and, so, it was restored when it was found that a file starts with 'scan-' and the directory matches the scancore agent directory.
* Moved the 'scancore' daemon's 'load_agent_strings' to 'Words'
* Updated Words->parse_banged_string() to look for variables in the format 'value=X:units=Y' and translate it properly.
* Fixed a bug in scan-ipmitool where discovered sensor INSERT SQL queries were queued, but not committed.
* Fixed a bug in scan-storcli where a while loop was broken, preventing execution.
* Fixed a bug in the 'scancore' daemon where it wouldn't exit if sums changed. Fixed a bug where alerts weren't being sent between loops. Fixed a bug where command-line log level wasn't surviving inside the main loop.
Signed-off-by: Digimer <digimer@alteeve.ca>
* Created Database->get_power() that loads data from the special 'power' table.
* Fixed a bug in calls to Network->ping() where some weren't formatted properly for receiving two string variables.
* Updated Database->get_anvils() to record the machine types when recording host information.
* Updated Database->get_hosts_info() to also load the 'host_ipmi' column.
* Updated Database->get_upses() to store the link to the 'power' -> 'power_uuid', when available.
* Created ScanCore->call_scan_agents() that does the work of actually calling scan agents, moving the logic out from the scancore daemon.
* Created ScanCore->check_power() that takes a host and the anvil it is in and returns if it's on batteries or not. If it is, the time on batteries and estimate hold-up time is returned. If not, the highest charge percentage is returned.
* Created ScanCore->post_scan_analysis() that is a wrapper for calling the new ->post_scan_analysis_dr(), ->post_scan_analysis_node() and ->post_scan_analysis_striker(). Of which, _dr and _node are still empty, but _striker is complete.
** ->post_scan_analysis_striker() is complete. It now boots a node after a power loss if the UPSes powering it are OK (at least one has mains power, and the main-powered UPS(es) have reached the minimum charge percentage). If it's thermal, IPMI is called and so long as at least one thermal sensor is found and it/they are all OK, it is booted. For now, M2's thermal reboot delay logic hasn't been replicated, as it added a lot of complexity and didn't prove practically useful.
* Created System->collect_ipmi_data() and moved 'scan_ipmitool's ipmitool call and parse into that method. This was done to allow ScanCore->post_scan_analysis_striker() to also call IPMI on a remote machine during thermal down events without reimplementing the logic.
* Updated scan-ipmitool to only record temperature data for data collected locally. Also renamed 'machine' variables and hash keys to 'host_name' to clarify what is being stored.
* Updated scancore to clear the 'system::stop_reason' variable.
* Added missing packages to striker-manage-install-target.
Signed-off-by: Digimer <digimer@alteeve.ca>
* Updated Database->insert_or_update_temperature() to accespt a 'delete' parameter (which, surprise, deletes a record).
* Updated (but not yet tested) the RPM .spec to require that 'core' and the other three packages are required to be the same version.
* Updated scan-ipmitool and scan-storcli scan agents to now delete temperature data belonging to lost sensors.
* Fixed tools/striker-manage-install-target to add multiple missing packages.
Signed-off-by: Digimer <digimer@alteeve.ca>
* Updated Alert->register() to take message variables using the 'variables' parameter.
* Added a 'cache' parameter to Database->insert_or_update_health() and ->insert_or_update_temperature(). When set, the SQL UPDATE/INSERT calls and pushed into the array reference set in 'cache'. This is to allow performance improvements when processing a large amount of sensor/device data.
* Updated Log->variables() to take a 'prefix' parameter that, when set, will prefix the string to each variable line.
* Updated scan-ipmitool to use Database->insert_or_update_health() and ->insert_or_update_temperature().
Signed-off-by: Digimer <digimer@alteeve.ca>
* Fixed a bug if Get->free_memory() where host_type was still being called from the old System->host_type method.
* Added global support for '--log-secure' and '--log-db' switches to enable logging of secure data and DB transactions, respectively.
* Created Database->get_tables_from_schema() that parses a SQL schema file and returns an array reference of tables found, in the order they were found.
* Updated ScanCore->agent_startup() to no longer require manually defining database tables, using Database->get_tables_from_schema() when not manually set.. Updated all existing agents to use this.
Signed-off-by: Digimer <digimer@alteeve.ca>